APPLIANCE WIRING MATERIAL | |||||
Subj.758 | Section 1 | Page 1024 | Issued:1959-05-01 | ||
Revised:2013-11-22 | |||||
Style 1024 | Single Conductor with extruded insulation | ||||
Rating | 90 deg C, 600 Vac, Horizontal flame. Optional - | ||||
60 deg C or 80 deg C Oil. | |||||
Conductor | 22 AWG - 8 AWG, Solid or Stranded. | ||||
Extruded PVC, 45 mils minimum average | |||||
Insulation | thickness, 40 mils minimum thickness at any point. | ||||
Standard | Appliance Wiring Material UL 758. | ||||
Marking | General. | ||||
Use | Internal Wiring. | ||||